B5h 04h - Get Data Block

Master/ Slave Byte-No. Abbrev. Description Unit Range Type/ [Res.] Repl. Value Note
M1 QQ Source address
M2 ZZ Target address
M3 PB = B5h Vaillant command
M4 SB = 04h Get Date/Time
M5 NN = 01h Length of data
M6 00h Data Block Identifer
M7 CRC
S1 ACK
S2 NN = 0Ah Length of data

Block 00h - Date/Time

Master/ Slave Byte-No. Abbrev. Description Unit Range Type/ [Res.] Repl. Value Note
M1 QQ Source address
M2 ZZ Target address
M3 PB = B5h Vaillant command
M4 SB = 04h Get Data Block
M5 NN = 01h Length of data
M6 DB = 00h Block 00h (Date/Time)
M7 CRC
S1 ACK
S2 NN = 0Ah Length of data
S3 00h
01h
02h
03h
DCF77 status:
no receiption
receiption
synchronized
data valid
BYTE
S4 ss Seconds Sec 0..59 BCD
S5 min Minutes Min 0..59 BCD
S6 hh Hours Hour 0..59 BCD
S7 dd Day 1..31 BCD
S8 mm Month 1..12 BCD
S9 ww Weekday 1..7 BCD
S10 yy Year 0..99 BCD
S11 TA_L Outside temperature °C -50,0 – 50,0 DATA2b [1/256]
S12 TA_H
S13 CRC
M8 ACK
M9 SYN

Block 01h - Unknown

Master/ Slave Byte-No. Abbrev. Description Unit Range Type/ [Res.] Repl. Value Note
M1 QQ Source address
M2 ZZ Target address
M3 PB = B5h Vaillant command
M4 SB = 04h Get Data Block
M5 NN = 01h Length of data
M6 DB = 00h Block 01h
M7 CRC
S1 ACK
S2 NN = 09h Length of data
S3 tt set temperature
- room: ZZ=26h
- service water: ZZ=25h
°C char 14h
S4 04h, 03h
S5 00h
S6 00h
S7 02h
S8 05h
S9 00h
S10 dd night=0 / day=1 On/Off char 00h
S11 00h
S12 CRC 2Ch
M8 ACK 00h
M9 SYN AAh

Block 02h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

HK1: 26h; WW:25h; ZP:23h

26h/25h/23h

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 02h

Block 02h

02h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 07h

Length of data

07h

S3

TB1

Zeitfenster1 Beginn

10Min

char

S4

TE1

Zeitfenster1 Ende

10Min

char

S5

TB2

Zeitfenster2 Beginn

10Min

char

S6

TE2

Zeitfenster2 Ende

10Min

char

S7

TB3

Zeitfenster3 Beginn

10Min

char

S8

TE3

Zeitfenster3 Ende

10Min

char

03h S9 DAY char

S9

CRC

B2h

M8

ACK

00h

M9

SYN

AAh

Block 09h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h 10h

M2

ZZ

Target address

23h 25h 26 50 EC

M3

PB = B5h

Vaillant command

B5h B5h

M4

SB = 04h

Get Data Block

04h 04h

M5

NN = 01h

Length of data

01h 01h

M6

DB = 09h

Block 09h

09h 09h

M7

CRC

CEh DAh

S1

ACK

00h 00h

S2

NN = 0Ah

Length of data

0Ah 0Ah

S3

RaumTemp

char

14h 37h

S4

AbsenkTemp

char

00h 00h

S5

Heizkurve * 10

char

00h 00h

S6

00h 00h

S7

06h 03h

S8

AT-AbschaltTemp

char

16h 16h

S9

00h 00h

S10

MinTempVL

char

0Fh 0Fh

S11

MaxTempVL

char

4Bh 5Ah

S12

00h 00h

S13

CRC

80h 4Eh

M8

ACK

00h 00h

M9

SYN

AAh AAh

Block 0Dh– service water

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

23h 25h 26 50 EC

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 0Dh

Block 0Dh

0Dh

M7

CRC

CAh

S1

ACK

00h

S2

NN = 05h

Length of data

05h

S3

VL_TT

flow set temperature

°C

char

00h S4

S5

TT_L

Temperature of the service water store (ZZ=25h)

Tempeature of flow water (Z=26h)

°C

DATA2c

00h

S6

TT_H

S7

R_TT

room set temperature

ZZ=26h

°C

char

00h

S8

CRC

4Ch

M8

ACK

00h

M9

SYN

AAh

Block 0Fh – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 0Fh

Block 0Fh

0Fh

M7

CRC

C7h

S1

ACK

00h

S2

NN = 0Ah

Length of data

0Ah

S3

XX = 14h

59h

S4

XX = 00h

03h

S5

XX = 00h

3Ch

S6

XX = 00h

03h

S7

XX = 06h

21h

S8

XX = 16h

FFh

S9

XX = 00h

21h

S10

XX = 0Fh

FFh

S11

XX = 4Bh

00h

S12

XX = 00h

00h

S13

CRC

E4h

M8

ACK

00h

M9

SYN

AAh

Block 10h – Temperatur Waterstorage

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 10h

Block 10h

10h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 0Ah

Length of data

0Ah

S3

TW1_L

Service-Water Temperatur 1

°C

DATA2C 	

50h

S4

TW1_H

0Ch

S5

TW2_L

Service-Water Temperatur 2

°C

DATA2C

08h

S6

TW2_H

50h

S7

TW3_L

Service-Water Temperatur 3

°C

DATA2C

07h

S8

TW3_H

03h

S9

TD1_L 	Tempeartursensor TD1 	°C 		DAT2C 		

S10

TD1_H 			

S11 TD2_L Tempeartursensor TD1 °C DATA2C S12 TD2_H

S10

CRC

B2h

M8

ACK

00h

M9

SYN

AAh

Block 11h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 11h

Block 11h

11h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 06h

Length of data

06h

S3

50h

S4

0Ch

S5

08h

S6

50h

S7

07h

S8

03h

S9

CRC

B2h

M8

ACK

00h

M9

SYN

AAh

Block 12h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 12h

Block 12h

12h

M7

CRC

DAh

S1

ACK

00h

S2

NN = 0Ah

Length of data

0Ah

S3

4Bh

S4

00h

S5

00h

S6

67h

S7

0Bh

S8

00h

S9

80h

S10

00h

S11

00h

S12

00h

S13

CRC

0Bh

M8

ACK

00h

M9

SYN

AAh

Block 17h – Service Water day time

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

25h

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 17h

Block 17h

17h

M7

CRC

DAh

S1

ACK

00h

S2

NN = 01h

Length of data

0Ah

S3

AA

Service time for Service water

OnOff

char

S4

CRC

M8

ACK

00h

M9

SYN

AAh

Block 18h – Heating-Lead-Temperature for HK2 (Mixer) incl. Raising-Temp. (Kessel-Soll für HK2 incl. Temperaturüberhöhung )

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

50h

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 17h

Block 17h

18h

M7

CRC

E7h

S1

ACK

00h

S2

NN = 01h

Length of data

06h

S3

HLT_KH2_L

Heizkessel-Solltemperatur für Versorgung HK2 mit Offset „Temperaturüberhöhung“

data2b

20h

S4

HLT_HK2_H

1fh S5 unknown - always 00h 00h S6 HK2_T_L Vorlauftemperatur HK2

		data2c 		9dh

S7 HK2_T_H 01h S8 unknown 15h or 13h S9 CRC 86h

M8

ACK

00h

M9

SYN

AAh

Block 21h – Service water storage

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 11h

Block 11h

11h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 05h

Length of data

05h

S3

CC

Collector temperature

°C

char

S4

DD

unkown

00h

S5

EE

heater source 0: off 1: solar 2: heater

char

S6

FF

Storage level

%

char

Entspricht der Füllstandsanzeige im IDLE-Display der Steuerung

S7

GG

Power

%

char

Entpsricht Balken- anzeige im Display

S8

CRC

M8

ACK

00h

M9

SYN

AAh

Block 22h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 12h

Block 11h

11h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 03h

Length of data

05h

S3

OO

unkown

00h

S4

PP

unkown

04h

S5

QQ

unkown

07h

S6

CRC

24h

M8

ACK

00h

M9

SYN

AAh

Block 25h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 25h

Block 25h

25h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 02h

Length of data

02h

S3

PP

unknown

07h

S4

QQ

unkown

03h

S5

CRC

D8h

M8

ACK

00h

M9

SYN

AAh

Block 26h – VR 81 remote control unit for VRC 430(f)/470(f)

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ = 30h

Source address

M2

ZZ = 26h

Target address

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 26h

Block 26h

26h

M7

CRC

S1

ACK

S2

NN = 07h

Length of data

S3

?

S4

MO

Current mode of operation:

00h=heating disabled, 02h=day, 03h=day, 04h=night

byte 	

S5

?

S6 RS Target room temperature °C data1c S7 ? S8 RC_L Current room temperature (corrected by offset value) °C data2c S9 RC_H

S10

CRC

M8

ACK

00h

M9

SYN

AAh

The current room temperature in this frame (bytes S8 and S9, RC_L and RC_H) is unreliable and should not be used! Instead, use the data from the frame (qq=30h, zz=26h, pb=B5h, sb=05h, nn=05h, first data byte 3Ch). Also note that the byte S6 has been found to be missing if the target room temperature is set to 22.0°C. It is unclear whether this is intentional or a bug.

Block 28h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 28h

Block 28h

28h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 03h

Length of data

05h

S3

SE_L

Solarertrag

kWh

word

S4

PP

S5

QQ

unkown

00h

S6

CRC

24h

M8

ACK

00h

M9

SYN

AAh

Block 36h – Unknown

Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address

10h

M2

ZZ

Target address

ECh

M3

PB = B5h

Vaillant command

B5h

M4

SB = 04h

Get Data Block

04h

M5

NN = 01h

Length of data

01h

M6

DB = 36h

Block 36h

36h

M7

CRC

D9h

S1

ACK

00h

S2

NN = 01h

Length of data

01h

S3

QQ

unkown

00h

S4

CRC

9Bh

M8

ACK

00h

M9

SYN

AAh

ebus/serviceb504.1444675285.txt.gz · Zuletzt geändert: 2015/10/14 19:13 (Externe Bearbeitung)