Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address











M2

ZZ

Target address











M3

PB = B5h

Vaillant command











M4

SB = 04h

Get Date/Time











M5

NN = 01h

Length of data











M6

00h

Data Block Identifer











M7

CRC













S1

ACK













S2

NN = 0Ah

Length of data


























Block 00h - Date/Time


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address











M2

ZZ

Target address











M3

PB = B5h

Vaillant command











M4

SB = 04h

Get Data Block











M5

NN = 01h

Length of data











M6

DB = 00h

Block 00h (Date/Time)











M7

CRC













S1

ACK













S2

NN = 0Ah

Length of data











S3


00h
01h
02h
03h

DCF77 status:

no receiption
receiption
synchronized
data valid





BYTE





S4

ss

Seconds

Sec

0..59

BCD





S5

min

Minutes

Min

0..59

BCD





S6

hh

Hours

Hour

0..59

BCD





S7

dd

Day



1..31

BCD





S8

mm

Month



1..12

BCD





S9

ww

Weekday



1..7

BCD





S10

yy

Year



0..99

BCD





S11

TA_L

Outside temperature

°C

-50,0 – 50,0

DATA2b [1/256]





S12

TA_H

S13

CRC













M8

ACK













M9

SYN












Block 01h - Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









26h

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 01h

Block 01h









01h

M7

CRC











D8h

S1

ACK











00h

S2

NN = 09h

Length of data









09h

S3

tt

set temperature

- room: ZZ=26h

- service water: ZZ=25h

°C



char



14h

S4













04h, 03h

S5













00h

S6













00h

S7













02h

S8













05h

S9













00h

S10

dd

night=0 / day=1

On/Off



char



00h

S11













00h

S12

CRC











2Ch

M8

ACK











00h

M9

SYN











AAh

Block 02h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address

HK1: 26h; WW:25h; ZP:23h









26h/25h/23h

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 02h

Block 02h









02h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 07h

Length of data









07h

S3

TB1

Zeitfenster1 Beginn



10Min





char







S4

TE1



Zeitfenster1 Ende



10Min





char







S5

TB2



Zeitfenster2 Beginn



10Min





char







S6

TE2



Zeitfenster2 Ende



10Min





char







S7

TB3



Zeitfenster3 Beginn



10Min





char







S8

TE3



Zeitfenster3 Ende



10Min





char





03h
S9DAY char

S9

CRC











B2h

M8

ACK











00h

M9

SYN











AAh

Block 09h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h 10h

M2

ZZ

Target address









23h 25h 26 50 EC

M3

PB = B5h

Vaillant command









B5h B5h

M4

SB = 04h

Get Data Block









04h 04h

M5

NN = 01h

Length of data









01h 01h

M6

DB = 09h

Block 09h









09h 09h

M7

CRC











CEh DAh

S1

ACK











00h 00h

S2

NN = 0Ah

Length of data









0Ah 0Ah

S3


RaumTemp
|

|

|
char
|

|
14h 37h
|


S4


AbsenkTemp
|

|

|
char
|

|
00h 00h
|


S5



Heizkurve * 10





char



00h 00h

S6













00h 00h

S7













06h 03h

S8



AT-AbschaltTemp





char



16h 16h

S9













00h 00h

S10


MinTempVL
|

|

|
char
|

|
0Fh 0Fh
|


S11


MaxTempVL
|

|

|
char
|

|
4Bh 5Ah
|


S12













00h 00h

S13

CRC











80h 4Eh

M8

ACK











00h 00h

M9

SYN











AAh AAh

Block 0Dh– service water


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









23h 25h 26 50 EC

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 0Dh

Block 0Dh









0Dh

M7

CRC











CAh

S1

ACK











00h

S2

NN = 05h

Length of data









05h

S3

VL_TT

flow set temperature

°C



char



00h
S4

S5

TT_L

Temperature of the service water store (ZZ=25h)

Tempeature of flow water (Z=26h)
°C
  \\   \\  |  \\   \\ |  \\ DATA2c \\  \\   \\ |  \\   \\ |  \\ 00h \\  \\   \\ |

S6

TT_H



S7

R_TT



room set temperature

ZZ=26h

°C





char





00h

S8

CRC











4Ch

M8

ACK











00h

M9

SYN











AAh

Block 0Fh – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 0Fh

Block 0Fh









0Fh

M7

CRC











C7h

S1

ACK











00h

S2

NN = 0Ah

Length of data









0Ah

S3

XX = 14h











59h

S4

XX = 00h











03h

S5

XX = 00h











3Ch

S6

XX = 00h











03h

S7

XX = 06h











21h

S8

XX = 16h











FFh

S9

XX = 00h











21h

S10

XX = 0Fh











FFh

S11

XX = 4Bh











00h

S12

XX = 00h











00h

S13

CRC











E4h

M8

ACK











00h

M9

SYN











AAh

Block 10h – Temperatur Waterstorage


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 10h

Block 10h









10h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 0Ah

Length of data









0Ah

S3

TW1_L



Service-Water Temperatur 1



°C




DATA2C


50h

S4

TW1_H







0Ch

S5

TW2_L



Service-Water Temperatur 2



°C




DATA2C


|

|
08h
|


S6

TW2_H







50h

S7

TW3_L



Service-Water Temperatur 3



°C




DATA2C


|

|
07h
|


S8

TW3_H







03h

S9
TD1_LTempeartursensor TD1°C DAT2C

S10
TD1_H
S11TD2_LTempeartursensor TD1°C DATA2C
S12TD2_H

S10

CRC











B2h

M8

ACK











00h

M9

SYN











AAh

Block 11h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 11h

Block 11h









11h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 06h

Length of data









06h

S3













50h

S4













0Ch

S5













08h

S6













50h

S7













07h

S8













03h

S9

CRC











B2h

M8

ACK











00h

M9

SYN











AAh

Block 12h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 12h

Block 12h









12h

M7

CRC











DAh

S1

ACK











00h

S2

NN = 0Ah

Length of data









0Ah

S3













4Bh

S4













00h

S5













00h

S6













67h

S7













0Bh

S8













00h

S9













80h

S10













00h

S11













00h

S12













00h

S13

CRC











0Bh

M8

ACK











00h

M9

SYN











AAh

Block 17h – Service Water day time


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









25h

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 17h

Block 17h









17h

M7

CRC











DAh

S1

ACK











00h

S2

NN = 01h

Length of data









0Ah

S3

AA

Service time for Service water

OnOff
|

|
char
|

|

|


S4

CRC













M8

ACK











00h

M9

SYN











AAh

===== Block 18h – Heating-Lead-Temperature for HK2 (Mixer) incl. Raising-Temp.
(Kessel-Soll für HK2 incl. Temperaturüberhöhung )


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









50h

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 17h

Block 17h









18h

M7

CRC











E7h

S1

ACK











00h

S2

NN = 01h

Length of data









06h

S3

HLT_KH2_L

Heizkessel-Solltemperatur für Versorgung HK2 mit Offset „Temperaturüberhöhung“







data2b





20h

S4

HLT_HK2_H







1fh
S5 unknown - always 00h 00h
S6HK2_T_LVorlauftemperatur HK2 data2c 9dh
S7HK2_T_H 01h
S8 unknown 15h or 13h
S9CRC 86h

M8

ACK









00h

M9

SYN











AAh

Block 21h – Service water storage


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 11h

Block 11h









11h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 05h

Length of data









05h

S3

CC

Collector temperature

°C



char





S4

DD

unkown









00h

S5

EE

heater source
0: off
1: solar
2: heater





char





S6

FF

Storage level

%



char



Entspricht der Füllstandsanzeige im IDLE-Display der Steuerung

S7

GG

Power

%



char



Entpsricht Balken- anzeige im Display

S8

CRC













M8

ACK











00h

M9

SYN











AAh

Block 22h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 12h

Block 11h









11h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 03h

Length of data









05h

S3

OO

unkown









00h

S4

PP

unkown









04h

S5

QQ

unkown









07h

S6

CRC











24h

M8

ACK











00h

M9

SYN











AAh

Block 25h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 25h

Block 25h









25h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 02h

Length of data









02h

S3

PP

unknown

07h

S4

QQ

unkown









03h

S5

CRC











D8h

M8

ACK











00h

M9

SYN











AAh

Block 26h – VR 81 remote control unit for VRC 430(f)/470(f)


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ = 30h

Source address











M2

ZZ = 26h

Target address











M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 26h

Block 26h









26h

M7

CRC













S1

ACK













S2

NN = 07h

Length of data











S3

?









S4

MO
Current mode of operation:
00h=heating disabled, 02h=day, 03h=day, 04h=night


byte




S5

?


S6RSTarget room temperature°C data1c
S7?
S8RC_LCurrent room temperature (corrected by offset value)°C data2c
S9RC_H

S10

CRC













M8

ACK











00h

M9

SYN











AAh

The current room temperature in this frame (bytes S8 and S9, RC_L and RC_H) is unreliable and should not be used! Instead, use the data from the frame (qq=30h, zz=26h, pb=B5h, sb=05h, nn=05h, first data byte 3Ch).
Also note that the byte S6 has been found to be missing if the target room temperature is set to 22.0°C. It is unclear whether this is intentional or a bug.

Block 28h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 28h

Block 28h









28h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 03h

Length of data









05h

S3

SE_L

Solarertrag

kWh





word







S4

PP







S5

QQ

unkown









00h

S6

CRC











24h

M8

ACK











00h

M9

SYN











AAh

Block 36h – Unknown


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address









10h

M2

ZZ

Target address









ECh

M3

PB = B5h

Vaillant command









B5h

M4

SB = 04h

Get Data Block









04h

M5

NN = 01h

Length of data









01h

M6

DB = 36h

Block 36h









36h

M7

CRC











D9h

S1

ACK











00h

S2

NN = 01h

Length of data









01h

S3

QQ

unkown









00h

S4

CRC











9Bh

M8

ACK











00h

M9

SYN











AAh


ebus/serviceb504.1444849980.txt.gz · Zuletzt geändert: 2015/10/14 19:13 von admin