ebus:serviceb510

Dies ist eine alte Version des Dokuments!


B5h 10h - Operational Data from Room Controller to Burner Control Unit


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address











M2

ZZ

Target address











M3

PB = B5h

Vaillant command











M4

SB = 10h

Operational Data from Room Controller to Burner Control Unit











M5

NN = 09h

Length of data











M6

xx1











unknown, always 00h

M7

xx2











unknown, always 00h

M8

LT

Lead water target temperature
(Vorlauftemperatur)

°C

0 – 100

DATA1c





M9

ST

Service water target temperature

°C

0 – 100

DATA1c





M10

xx3











unknown, always FFh

M11

xx4











unknown, always FFh

M12

xx5 = 00h

= 01h
= 04h
= 05h
= 40h
= 41h
= 44h
= 45h







Bits:

01 - if set, means to TURN OFF heating

04 - if set means to TURN OFF service water heating

40 - unknown?



combination of bit values. Each bit means to turn off specific feature, like service water heating. This is used by the room controller to stop the boler from heating (when the temperature is enough), or stop service water heating

M13

xx6











unknown, always FFh

M14

xx7











unknown, always 00h

M15

CRC













S1

ACK













S2

NN = 01h

Length of data











S3

zz = 01h

(acknowledge ?)









unknown

S4

CRC













M16

ACK













M17

SYN