Master/ Slave Byte-No. | Abbrev. | Description | Unit | Range | Type/ [Res.] | Repl. Value | Note |
M1 | | Source address | | | | | |
M2 | ZZ | Target address | | | | | |
M3 | PB = B5h | Vaillant command | | | | | |
M4 | SB = 11h | Operational Data | | | | | |
M5 | NN = 01h | Length of data | | | | | |
M6 | 01h | Block number | | | | | |
M7 | CRC | | | | | | |
S1 | ACK | | | | | | |
S2 | NN = 09h | Length of data | | | | | |
S3 | VT | Lead water temperature (Vorlauf-/ Anlagentemperatur) | °C | 0 – 100 | DATA1c | | |
S4 | NT | Return water temperature (Nachlauftemperatur) | °C | 0 – 100 | DATA1c | | |
S5 | TA_L | Outside temperature | °C | -50,0 – 50,0 | DATA2b [1/256] | | |
S6 | TA_H |
||||||
S7 | WT | (WW-Auslauftemperatur) | °C | 0 – 100 | DATA1c | | |
S8 | ST | Service water temperature (WW-Speichertemperatur) | °C | 0 – 100 | DATA1c | | |
S9 | vv | Bit 0: Heating Bit 1: Service Water | | | BIT | | 0 = OFF 1 = ON |
S10 | xx1 | | | | | | unknown, always 00h |
S11 | xx2 | | | | | | unknown, always FFh |
S12 | CRC | | | | | | |
M8 | ACK | | | | | | |
M9 | SYN | | | | | | |
Master/ Slave Byte-No. | Abbrev. | Description | Unit | Range | Type/ [Res.] | Repl. Value | Note |
M1 | | Source address | | | | | |
M2 | ZZ | Target address | | | | | |
M3 | PB = B5h | Vaillant command | | | | | |
M4 | SB = 11h | Operational Data | | | | | |
M5 | NN = 01h | Length of data | | | | | |
M6 | 02h | Block number | | | | | |
M7 | CRC | | | | | | |
S1 | ACK | | | | | | |
S2 | NN = 05h | Length of data | | | | | |
S3 | xx1 | | | | | | unknown, always 03h |
S4 | xx2 | | | | | | unknown, always 3Ch |
S5 | xx3 | | | | | | unknown, always 96h |
S6 | xx4 | | | | | | unknown, always 46h |
S7 | ST | Service water target temperature | °C | 0 – 100 | DATA1c | | |
S8 | CRC | | | | | | |
M8 | ACK | | | | | | |
M9 | SYN | | | | | |