Master/ Slave Byte-No. | Abbrev. | Description | Unit | Range | Type/ [Res.] | Repl. Value | Note |
M1 | | Source address | | | | | |
M2 | ZZ | Target address | | | | | |
M3 | PB = B5h | Vaillant command | | | | | |
M4 | SB = 12h | Unknown command [ping ?] | | | | | |
M5 | NN = 02h | Length of data | | | | | |
M6 | xx | ? | | | | | |
M7 | yy | ? | | | | | |
M8 | CRC | | | | | | |
S1 | ACK | | | | | | |
S2 | NN = 00h | Length of data | | | | | |
S3 | CRC | | | | | | |
M9 | ACK | | | | | | |
M10 | SYN | | | | | | |
The following cases were observed:
Heater Controller (Master 10h) → Firing Automat 1 (Slave 08h):
(xx = 00h, yy = 00h) hot water circulating pump is off
(xx = 00h, yy = 64h) hot water circulating pump is on
Firing Automat 1 (Master 03h) → Pump 1 (Slave 64h):
(xx = 02h, yy = 00h) internal pump is off
(xx = 02h, yy = 64h) internal pump is on and operating in the service water circuit
(xx = 02h, yy = FEh) internal pump is on and operating in the heating circuit
(xx = 03h, yy = 00h) internal pump is disabled due to error condition (such as water pressure too low)
Firing Automat 1 (Master 03h) → PC/ Modem (Slave 05h):
(xx = 03h, yy = 00h)