Benutzer-Werkzeuge

Webseiten-Werkzeuge


ebus:serviceb516

B5h 16h 00h - Broadcast Service

Date/Time:

Master/ Slave Byte-No. Abbrev. Description Unit Range Type/ [Res.] Repl. Value Note
M1 QQ Source address
M2 ZZ = FEh Target address Broadcast
M3 PB = B5h Vaillant command
M4 SB = 16h Broadcast Service
M5 NN = 08h Length of data
M6 00h Broadcast Date/Time
M7 ss Seconds Sec 0..59 BCD
M8 min Minutes Min 0..59 BCD
M9 hh Hours Hour 0..59 BCD
M10 dd Day 1..31 BCD
M11 mm Month 1..12 BCD
M12 ww Weekday 1..7 BCD
M13 yy Year 0..99 BCD
M14 CRC
M15 SYN

B5h 16h 01h - Broadcast Service

Outside Temperature:

Master/ Slave Byte-No. Abbrev. Description Unit Range Type/ [Res.] Repl. Value Note
M1 QQ Source address
M2 ZZ = FEh Target address Broadcast
M3 PB = B5h Vaillant command
M4 SB = 16h Broadcast Service
M5 NN = 03h Length of data
M6 01h Broadcast outside temperature
M7 TA_L Outside temperature °C -50,0 – 50,0 DATA2b [1/256]
M8 TA_H
M14 CRC
M15 SYN

.


ebus/serviceb516.txt · Zuletzt geändert: 2015/10/14 19:58 (Externe Bearbeitung)