B5h 16h 00h - Broadcast Service

Date/Time:


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address











M2

ZZ = FEh

Target address









Broadcast

M3

PB = B5h

Vaillant command











M4

SB = 16h

Broadcast Service











M5

NN = 08h

Length of data











M6

00h

Broadcast Date/Time











M7

ss

Seconds

Sec

0..59

BCD





M8

min

Minutes

Min

0..59

BCD





M9

hh

Hours

Hour

0..59

BCD





M10

dd

Day



1..31

BCD





M11

mm

Month



1..12

BCD





M12

ww

Weekday



1..7

BCD





M13

yy

Year



0..99

BCD





M14

CRC













M15

SYN












B5h 16h 01h - Broadcast Service

Outside Temperature:


Master/ Slave Byte-No.

Abbrev.

Description

Unit

Range

Type/ [Res.]

Repl. Value

Note

M1

QQ

Source address











M2

ZZ = FEh

Target address









Broadcast

M3

PB = B5h

Vaillant command











M4

SB = 16h

Broadcast Service











M5

NN = 03h

Length of data











M6

01h

Broadcast outside temperature











M7

TA_L

Outside temperature

°C

-50,0 – 50,0

DATA2b [1/256]





M8

TA_H

M14

CRC













M15

SYN












.